The gas flare was intended for a research project that could not be
carried out. It is brand new and in its original packaging.
The torch is supplied as a complete "package unit" with an on-site
control cabinet made of CrNi steel. The torch can be installed both
indoors and outdoors, but the torch should be visible to the operator
of the control cabinet.
1.1 Pilot burner / biogas support burner with fittings
The equipment of the pilot biogas burner unit consists of the
following components:
- Shut-off ball valve DN25, approved for biogas
- Biogas filter DN25
- Pressure regulator DN25
- Pressure gauge with "push-button shutdown", 0-100 mbar, approved for
biogas
- Gas solenoid valve DN 25, make: Kromschröder, type VAS 125R/LW
- Flame arrester DN25, make: Protego, FA-G1" IIA1-P2,2
- Biogas burner nozzle (4 pcs.)
1.2 Process gas burners with fittings
The equipment of the process gas burner unit consists of the following
components:
- Butterfly valve DN80
- Pressure gauge with "push-button shutdown", 0-1.6 bar
- Gas engine valve, 2-stage, DN80, make: Kromschröder, type
VK80F24ZT5A93DS
- Flame arrester DN80, make: Protego, FA-E-T-80-IIC-P1,1
- Temperature monitoring flame retardant (PT100), adjustable 60°C -
120°C
- Process gas burner nozzle V5661893 (1 pc.)
1.3 Ignition and protection / monitoring fitting
The two burner units are ignited or monitored by the following
components:
- Electronic ignition electrodes (1 pair) with transformer
- UV probe
- 1 thermocouple in the flame tube (1.4 mtr long)
- LCD temperature display and evaluation device,
Make: OMRON, type K3HB-R
1.4 Drainage or condensate outlet
To drain any condensate that may occur in the process gas system,
there is a ball valve in the vertical process gas line.
Any condensate can be discharged via the ball valve.